Iskra iHUB and iHUB Lite

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Iskra
  • Equipment: iHUB and iHUB Lite
  • Vulnerability: Missing Authentication for Critical Function

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow a remote attacker to reconfigure devices, update firmware, and manipulate connected systems without any credentials.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Iskra iHUB and iHUB Lite, a Smart Metering Gateway and Data Concentrator, are affected:

  • iHUB and iHUB Lite: All Versions

3.2 VULNERABILITY OVERVIEW

3.2.1 Missing Authentication for Critical Function CWE-306

The Iskra iHUB and iHUB Lite smart metering gateway exposes its web management interface without requiring authentication, allowing unauthenticated users to access and modify critical device settings.

CVE-2025-13510 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2025-13510. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND