Summary
Successful exploitation of these vulnerabilities could allow an attacker to retrieve sensitive system information, access application data without authorization, recover stored credentials, or intercept and manipulate network communications.
The following versions of Dorsett Controls InfoScan are affected:
- InfoScan <=1.45.0 (CVE-2026-117659, CVE-2026-120157, CVE-2026-120255, CVE-2026-120260, CVE-2026-120271, CVE-2026-120298)
CVSS
Vendor
Equipment
v3 8.1
Dorsett Controls
InfoScan
5 Vulnerabilities
Improper Certificate Validation, Exposure of Sensitive System Information to an Unauthorized Control Sphere, Use of Hard-coded Cryptographic Key, Missing Authentication for Critical Function, Generation of Error Message Containing Sensitive Information
Background
- Critical Infrastructure Sectors: Water and Wastewater Systems
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: United States
Vulnerabilities
Expand All +
CVE-2026-117659
The InfoScan Electron desktop client improperly handles TLS certificate errors by accepting certificates without validating their trustworthiness. The client also configures Electron with nodeIntegration enabled, contextIsolation disabled, and webSecurity disabled. These settings weaken the client’s security boundaries. An attacker who is able to intercept or manipulate network communications may be able to present an untrusted certificate without the application rejecting the connection.
Read More
1 Affected Product
Dorsett Controls InfoScan <=1.45.0
Product Status: known_affected
Remediations
Vendor fix
Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher. To install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.
Additional Metrics
Relevant CWE: CWE-295 Improper Certificate Validation
CVSS Version
Base Score
Base Severity
Vector String
3.1
8.1
HIGH
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N
4.0
8.5
HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N
CVE-2026-120157
The publicly distributed InfoScan Electron installer contains configuration files identifying hostnames associated with customer installations and internal development, testing, and database infrastructure. An individual who obtains and inspects the installer can extract these hostnames without authenticating to the affected systems.
Read More
2 Affected Products
Dorsett Controls InfoScan <=1.45.0
Product Status: known_affected
Remediations
Vendor fix
Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher. To install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.
Dorsett Controls InfoScan <=1.45.0
Product Status: known_affected
Remediations
Vendor fix
Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher. To install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.
Additional Metrics
Relevant CWE: CWE-497 Exposure of Sensitive System Information to an Unauthorized Control Sphere
CVSS Version
Base Score
Base Severity
Vector String
3.1
5.3
MEDIUM
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
4.0
6.9
MEDIUM
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N
CVE-2026-120255
InfoScan uses hard-coded cryptographic keys and initialization-vector values in its database-encryption implementation. The application uses these values to encrypt the MongoDB password before storing it in the Windows registry. Because the cryptographic material is embedded in the distributed
[…]
Content was trimmed to protect the source. Please visit the original article for the full text.