Siemens SIMATIC

View CSAF

Summary

The products listed below contain an authentication bypass vulnerability that could allow an on-path attacker to take over the session of a legitimate user and execute arbitrary code with the privileges of the victim user. Siemens is preparing fixes and recommends specific mitigations for products where fixes are not or not yet available.

The following versions of Siemens SIMATIC are affected:

  • SIMATIC BATCH V9.1 vers:all/* (CVE-2026-58114)
  • SIMATIC Information Server 2020 vers:all/* (CVE-2026-58114)
  • SIMATIC Information Server 2022 vers:all/* (CVE-2026-58114)
  • SIMATIC PCS 7 V9.1 vers:all/* (CVE-2026-58114)
  • SIMATIC Process Historian 2020 vers:all/* (CVE-2026-58114)
  • SIMATIC Process Historian 2022 vers:all/* (CVE-2026-58114)
  • SIMATIC WinCC Runtime Professional V17 vers:all/* (CVE-2026-58114)
  • SIMATIC WinCC Runtime Professional V18 vers:all/* (CVE-2026-58114)
  • SIMATIC WinCC Runtime Professional V19 vers:all/* (CVE-2026-58114)
  • SIMATIC WinCC Runtime Professional V20 vers:all/* (CVE-2026-58114)
  • SIMATIC WinCC Runtime Professional V21 vers:all/* (CVE-2026-58114)
  • SIMATIC WinCC V7.5 vers:all/* (CVE-2026-58114)
  • SIMATIC WinCC V8.0 vers:all/* (CVE-2026-58114)
  • SIMATIC WinCC V8.1 vers:all/* (CVE-2026-58114)

CVSS
Vendor
Equipment

v3 7.5
Siemens
SIMATIC BATCH V9.1

1 Vulnerability

Weak Authentication

Background

  • Critical Infrastructure Sectors: Critical Manufacturing
  • Countries/Areas Deployed: Worldwide
  • Company Headquarters Location: Germany

Vulnerabilities

CVE-2026-58114
Affected systems do not properly secure their remote user authentication with the deprecated NTLM protocol. This could allow unauthenticated remote attackers, who have achieved a machine in the middle position, to relay NTLM authentication and impersonate a legitimate user. The potential impact depends on the services that are accessible, e.g. a SQL server used by WinCC.
Read More

14 Affected Products

SIMATIC BATCH V9.1

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

No fix planned
Currently no fix is planned

SIMATIC WinCC Runtime Professional V20

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

None available
Currently no fix is available

SIMATIC WinCC Runtime Professional V21

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

None available
Currently no fix is available

SIMATIC WinCC V7.5

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

None available
Currently no fix is available

SIMATIC WinCC V8.0

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

None available
Currently no fix is available

SIMATIC WinCC V8.1

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

None available
Currently no fix is available

SIMATIC Information Server 2020

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

No fix planned
Currently no fix is planned

SIMATIC Information Server 2022

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

No fix planned
Currently no fix is planned

SIMATIC PCS 7 V9.1

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

No fix planned
Currently no fix is planned

SIMATIC Process Historian 2020

Product Status: known_affected

Remediations

Mitigation
Customers can manually configure the SQL Server Database for encrypting communication as described in https://support.industry.siemens.com/cs/mdm/109818202?c=145291786635&lc=en-ID

No fix

[…]
Content was trimmed to protect the source. Please visit the original article for the full text.

This article has been indexed from All CISA Advisories

Read the original article:

Siemens SIMATIC