Summary
Successful exploitation this vulnerability could allow an attacker to gain unauthorized access to sensitive files
The following versions of Schneider Electric EasyLogic T150 and Saitel DP are affected:
- Schneider Electric EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller Firmware installed on Schneider Electric EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller (All versions) vers:semver/<=11.06.31 (CVE-2026-6865)
- Schneider Electric Saitel DP Remote Terminal Unit & Controller Firmware installed on Schneider Electric Saitel DP Remote Terminal Unit & Controller (All versions) vers:semver/<=11.06.36 (CVE-2026-6865)
| CVSS | Vendor | Equipment | Vulnerabilities |
|---|---|---|---|
| v3 7.1 | Schneider Electric | Schneider Electric EasyLogic T150 and Saitel DP | Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’) |
Background
- Critical Infrastructure Sectors: Energy, Critical Manufacturing
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: France
Vulnerabilities
CVE-2026-6865
CWE-22: Improper Limitation of a Pathname to a Restricted Directory (“Path Traversal”) vulnerability that could cause unauthorized access to sensitive files when user-supplied input is improperly handled during server-side file path processing.
Affected Products
Schneider Electric EasyLogic T150 and Saitel DP
Schneider Electric
Schneider Electric Schneider Electric EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller Firmware installed on Schneider Electric EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller (All versions): vers:semver/<=11.06.31, Schneider Electric Schneider Electric Saitel DP Remote Terminal Unit & Controller Firmware installed on Schneider Electric Saitel DP Remote Terminal Unit & Controller (All versions): vers:semver/<=11.06.36
known_affected
Remediations
Mitigation
Schneider Electric has identified the following specific workarounds and mitigations users can apply to reduce risk: Schneider Electric EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller Firmware (vers:semver/<=11.06.31) installed on Schneider Electric EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller (All versions): Version 11.06.32 of EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller includes a fix for this vulnerability and is available for download here:
Mitigation
Contact Schneider Electric’s Customer Care Center to download this firmware. Reboot needed: Yes
Mitigation
Schneider Electric Saitel DP Remote Terminal Unit & Controller Firmware (vers:semver/<=11.06.36) installed on Schneider Electric Saitel DP Remote Terminal Unit & Controller (All versions): Version 11.06.37 of Saitel DP Remote Terminal Unit & Controller includes a fix for this vulnerability and is available for download here:
Mitigation
Contact Schneider Electric’s Customer Care Center to download this firmware. Reboot needed: Yes
Mitigation
All affected products: If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: Ensure strict credential controls, even for low privilege users.
Mitigation
Ensure isolation and credentials are in place, as per the product’s security recommendations.
Mitigation
The following product versions have been fixed: Firmware Version 11.06.32 installed on EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller are fixed versions for CVE-2026-6865