Summary
Successful exploitation of this vulnerability could allow several unauthenticated admin accounts to be created.
The following versions of Autonomy Logic OpenPLC Runtime are affected:
- OpenPLC Runtime <=4.2.4 (CVE-2026-126088)
CVSS
Vendor
Equipment
v3 8.1
Autonomy Logic
OpenPLC Runtime
1 Vulnerability
Concurrent Execution using Shared Resource with Improper Synchronization ('Race Condition')
Background
- Critical Infrastructure Sectors: Critical Manufacturing, Energy, Transportation Systems, Water and Wastewater Systems
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: United States
Vulnerabilities
CVE-2026-126088
In Autonomy Logic OpenPLC Runtime versions 4.2.4 and prior, a race condition allows multiple concurrent requests to pass the existence check before any user is committed, resulting in several unauthenticated admin accounts being created.
Read More
1 Affected Product
Autonomy Logic OpenPLC Runtime <=4.2.4
Product Status: known_affected
Remediations
Vendor fix
Update to OpenPLC Runtime version 4.3.0 or later.
Additional Metrics
Relevant CWE: CWE-362 Concurrent Execution using Shared Resource with Improper Synchronization ('Race Condition')
CVSS Version
Base Score
Base Severity
Vector String
3.1
8.1
HIGH
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H
4.0
9.2
CRITICAL
CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Acknowledgments
- Noureddin Lutfi reported this vulnerability to CISA.
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
Revision History
- Initial Release Date: 2026-11-19
Date
Revision
Summary
2026-11-19
1
Initial Publication
Legal Notice and Terms of Use
Read the original article: