Summary
.NET Client Library for SIMATIC S7 Webserver API contains multiple vulnerabilities that could allow an attacker to obtain sensitive information or write arbitrary files outside the intended download directory. Siemens has released a new version for .NET Client Library for SIMATIC S7 Webserver API and recommends to update to the latest version.
The following versions of Siemens SIMATIC S7 Webserver API are affected:
- .NET Client Library for SIMATIC S7 Webserver API vers:intdot/<3.3.61, vers:intdot/<3.3.62 (CVE-2026-85114, CVE-2026-85115)
CVSS
Vendor
Equipment
v3 7.5
Siemens
.NET Client Library for SIMATIC S7 Webserver API
2 Vulnerabilities
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal'), Generation of Error Message Containing Sensitive Information
Background
- Critical Infrastructure Sectors: Critical Manufacturing, Transportation Systems, Energy, Healthcare and Public Health, Financial Services, Government Services and Facilities
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: Germany
Vulnerabilities
Expand All +
CVE-2026-85114
Affected applications do not properly validate filenames received from remote servers during ticket downloads. This could allow an attacker who can manipulate the ticket response to write arbitrary files outside the intended download directory and, when overwriting is enabled, replace existing files accessible to the application.
Read More
1 Affected Product
.NET Client Library for SIMATIC S7 Webserver API < V3.3.61
Product Status: known_affected
Remediations
Vendor fix
Update to V3.3.61 or later version
Additional Metrics
Relevant CWE: CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')
CVSS Version
Base Score
Base Severity
Vector String
3.1
7.5
HIGH
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
CVE-2026-85115
Affected applications do not properly redact PLC restore passwords from HTTP error exception messages. This could allow an attacker with access to logs or other diagnostic output to obtain the plaintext restore password and potentially perform unauthorized operations on the PLC.
Read More
2 Affected Products
.NET Client Library for SIMATIC S7 Webserver API < V3.3.61
Product Status: known_affected
Remediations
.NET Client Library for SIMATIC S7 Webserver API < V3.3.62
Product Status: known_affected
Remediations
Vendor fix
Update to V3.3.62 or later version
Additional Metrics
Relevant CWE: CWE-209 Generation of Error Message Containing Sensitive Information
CVSS Version
Base Score
Base Severity
Vector String
3.1
5.5
MEDIUM
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N
Acknowledgments
- Siemens ProductCERT reported these vulnerabilities to CISA.
General Recommendations
As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are
[…]
Content was trimmed to protect the source. Please visit the original article for the full text.